Fuzzy logic based on-line fault detection and classification in transmission line

Shuma Adhikari1, Nidul Sinha2, Thingam Dorendrajit1

  • 1Department of Electrical Engineering, National Institute of Technology Manipur, Imphal, Manipur India.

Springerplus
|July 12, 2016
PubMed

Related Concept Videos

Fault Types01:18

Fault Types

When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.
For line-to-line faults occurring between phases B and C, the...
478
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
613
Line Protection with Impedance Relays01:27

Line Protection with Impedance Relays

Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
494
Lossy Lines and Overvoltages01:22

Lossy Lines and Overvoltages

Transmission-line series resistance and shunt conductance cause three primary effects: attenuation, distortion, and power losses.
Attenuation
When constant series resistance and shunt conductance are present, voltage and current equations are modified. The propagation constant indicates that voltage and current waves consist of both forward and backward traveling components. These waves attenuate as they propagate, with the attenuation factor related to the resistance and conductance. In a...
382
Transmission-Line Differential Equations01:26

Transmission-Line Differential Equations

Transmission lines are essential components of electrical power systems. They are characterized by the distributed nature of resistance (R), inductance (L), and capacitance (C) per unit length. To analyze these lines, differential equations are employed to model the variations in voltage and current along the line.
Line Section Model
A circuit representing a line section of length Δx helps in understanding the transmission line parameters. The voltage V(x) and current i(x) are measured from...
1.1K
Transmission Line Design Considerations01:23

Transmission Line Design Considerations

Aluminum has become the material of choice for overhead transmission lines, surpassing copper due to its abundance and cost-effectiveness. The most prevalent type is the aluminum conductor, steel-reinforced (ACSR), which combines aluminum strands around a steel core. Other variants include all-aluminum conductors (AAC), all-aluminum alloy conductors (AAAC), aluminum conductor alloy-reinforced (ACAR), and aluminum-clad steel conductors. Advanced designs, such as aluminum conductors with steel...
699