Antlion optimizer-ANFIS load frequency control for multi-interconnected plants comprising photovoltaic and wind
1Electrical Engineering Department, Faculty of Engineering, Jouf University, Al-Jouf, Saudi Arabia; Electrical Power & Machine Department, Faculty of Engineering, Zagazig University, Zagazig, Egypt.
Abstract:
This paper proposes optimal load frequency control (LFC) designed by Adaptive Neuro Fuzzy Inference System (ANFIS) trained via antlion optimizer (ALO) for multi-interconnected system comprising renewable energy sources (RESs). Two systems are modeled and investigated; the first one has two plants of grid connected photovoltaic (PV) system with maximum power point tracker (MPPT) and thermal plant while the second comprises four plants of thermal, wind turbine and grid connected PV systems. ALO is employed to get the optimal gains of Proportional-Integral (PI) controller such that the integral time absolute error (ITAE) of frequency and tie line power deviations is minimized. The input and output of the optimized PI controller are used to train the ANFIS-LFC with Gaussian surface membership functions. Different load disturbances are studied and the results are compared with other reported approaches. The obtained results confirmed the accuracy and reliability of the proposed approach in designing LFC for multi-interconnected power systems.
Related Concept Videos
Load-frequency control
Wind Turbine Machine Models
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
Turbine-Governor Control
Frequency-Domain Interpretation of PD Control
The proportional control gain, combined with the...
Time and frequency -Domain Interpretation of PI Control
Acting as a low-pass filter, the PI controller slows the system's response and extends settling times. This requires...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...