A fast fault current calculation method for distribution networks connected with inverter interfaced distributed

Yingliang Li1, Deming Wang1

  • 1School of Electronic Engineering, Xi'an Shiyou University, Xi'an 710065, China.

Methodsx
|December 23, 2020
PubMed

Related Concept Videos

Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
400
Bus Impedance Matrix01:24

Bus Impedance Matrix

Calculating subtransient fault currents for three-phase faults in an N-bus power system involves using the positive-sequence network. When a three-phase short circuit occurs at a specific bus, the analysis uses the superposition method to evaluate two separate circuits.
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
395
Fast Decoupled and DC Powerflow01:24

Fast Decoupled and DC Powerflow

The fast decoupled power flow method addresses contingencies in power system operations, such as generator outages or transmission line failures. This method provides quick power flow solutions, essential for real-time system adjustments. Fast decoupled power flow algorithms simplify the Jacobian matrix by neglecting certain elements, leading to two sets of decoupled equations:
434
Fault Types01:18

Fault Types

When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.
For line-to-line faults occurring between phases B and C, the...
315
Primary Distribution01:28

Primary Distribution

Primary distribution systems deliver electrical power from substations to consumers through various voltage classes, with 15-kV class voltages being predominant among U.S. utilities. Older 2.5- and 5-kV classes are being replaced by 15-kV primaries, while higher 25- to 34.5-kV classes are used in high-density urban areas and rural regions with long feeders. Three-phase, four-wire multigrounded systems are widely employed for balanced power delivery, using the neutral wire as a grounding point.
434
Control of Power Flow01:30

Control of Power Flow

There are several methods to control power flow in power systems:
394