DDosTC: A Transformer-Based Network Attack Detection Hybrid Mechanism in SDN.

Haomin Wang1, Wei Li1

  • 1School of Control and Computer Engineering, North China Electric Power University, No. 2 Beinong Road, Changping District, Beijing 102206, China.

Summary

A new hybrid neural network, DDosTC, effectively detects distributed denial-of-service (DDoS) attacks in software-defined networking (SDN). This advanced model outperforms existing methods in accuracy and detection rates.

Related Concept Videos

Zones of Protection01:16

Zones of Protection

In power systems, the entire setup is divided into protective zones to isolate faults and protect the rest of the network. These zones include generators, transformers, buses, transmission lines, distribution lines, and motors. Each zone can be visualized as a separate room in a house, with each room protected by its own circuit breaker.
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
424
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
192
Network Function of a Circuit01:25

Network Function of a Circuit

Frequency response analysis in electrical circuits provides vital insights into a circuit's behavior as the frequency of the input signal changes. The transfer function, a mathematical tool, is instrumental in understanding this behavior. It defines the relationship between phasor output and input and comes in four types: voltage gain, current gain, transfer impedance, and transfer admittance. The critical components of the transfer function are the poles and zeros.
440
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
180
Differential Relays01:20

Differential Relays

Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
315
Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
1.1K