Associations between illness-related absences and ventilation and indoor PM2.5 in elementary schools of the Midwestern United States
Related Experiment Video
Updated: Jul 29, 2025

Composition and Distribution Analysis of Bioaerosols Under Different Environmental Conditions
Published on: January 7, 2019
Shihan Deng1, Josephine Lau2, Zhihao Wang3
1Faculty of Civil Engineering and Mechanics, Kunming University of Science and Technology, 727 South Jingming Road, Chenggong District, Kunming, Yunnan, 650500, China; Durham School of Architectural Engineering and Construction, University of Nebraska - Lincoln, 1110 S. 67th Street, Omaha, NE, 68182-0816, United States.
Abstract:
This study monitored indoor environmental data in 144 classrooms in 31 schools in the Midwestern United States for two consecutive days every fall, winter, and spring during a two-year period; 3,105 pupils attended classrooms where the measurements were conducted. All classrooms were ventilated with mechanical systems that had recirculation; there were no operable exterior windows or doors. The daily absence rate at the student level and demographic data at the classroom level were collected. The overall mean ventilation rate, using outdoor air, was 5.5 L/s per person (the corresponding mean carbon dioxide concentrations were < 2,000 ppm), and the mean indoor PM2.5 was 3.6 μg/m3. The annual illness-related absence rate at the classroom level was extracted from the student-level absence data and regressed on measured indoor environmental parameters. Significant associations were found. Every 1 L/s per person increase in ventilation rate was associated with a 5.59 decrease in days with absences per year. This corresponds to a 0.15% increase in the annual daily attendance rate. Every additional 1 μg/m3 of indoor PM2.5 was associated with a 7.37 increase in days with absences per year. This corresponds to a 0.19% decrease in the annual daily attendance rate. No other relationships were significant. Present results agree with the previously demonstrated benefits of reduced absence rates when classroom ventilation is improved and provide additional evidence on the potential benefits of reducing indoor inhalable particles. Overall, reduced absence rates are expected to provide socioeconomic benefits and benefits for academic achievements, while higher ventilation rates and reduced particle levels will also contribute to reduced health risks, including those related to airborne respiratory pathogens.
Related Concept Videos
Assessment of Ventilation II: Respiratory Depth and Rhythm
Respiratory depth measures the volume of air inhaled or exhaled during a breath. It can vary from shallow to deep and typically remains consistent when a person is at rest or asleep. Occasionally, individuals will automatically inhale deeply, known as sighing, which inflates the lungs with more air than normal breathing.
To assess respiratory depth, observe the degree of chest excursion or movement:
Assessment of Ventilation I: Respiratory Rate
A Ventilation assessment is critical for monitoring a patient's health status. Respiration, one of the most accessible vital signs, provides insights into the function of numerous body systems and can indicate serious health issues, such as brainstem injuries from head trauma.
Critical Guidelines for Assessing Ventilation:
Asthma-I: Introduction
Asthma-III: Symptoms and Complications
Classification of Asthma
Factors Affecting Pulmonary Ventilation
Alveolar Surface Tension
The alveolar fluid lines the luminal surface of the alveoli and exerts a force called surface tension. This force is caused by the polar water molecules in the liquid being more strongly attracted to each...
Respiratory System Abnormal Finding I: Inspection and Percussion
Inspection Findings
During an inspection, several findings may suggest the presence of respiratory distress or disease. Pursed-lip breathing, where exhalation is slowed by...