Incorporating Modern Fault Ride-Through Standards into the Short-Circuit Calculation of Distribution Networks.

Evangelos E Pompodakis1, Yiannis Katsigiannis2, Emmanuel S Karapidakis2

  • 1Institute of Energy, Environment and Climatic Change, Hellenic Mediterranean University, 71004 Heraklion, Greece.

PubMed
Summary

Modern fault ride-through standards mean short-circuit currents vary, complicating protective device tripping time calculations. This study improves accuracy by accounting for these dynamic fault currents in power grids with distributed generators.

Related Concept Videos

Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
93
Reclosers and Fuses01:26

Reclosers and Fuses

Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
114
Bus Impedance Matrix01:24

Bus Impedance Matrix

Calculating subtransient fault currents for three-phase faults in an N-bus power system involves using the positive-sequence network. When a three-phase short circuit occurs at a specific bus, the analysis uses the superposition method to evaluate two separate circuits.
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
128
Fault Types01:18

Fault Types

When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.
For line-to-line faults occurring between phases B and C, the...
90
Directional Relays01:25

Directional Relays

Directional relays, essential for managing unidirectional fault currents, enhance the safety and efficiency of power systems. On power lines equipped with directional relays, faults downstream (to the right) of the current transformer typically cause the fault current to lag the bus voltage by approximately 90 degrees, known as the forward direction. In contrast, upstream (left-side) faults may result in the fault current leading the bus voltage by nearly 90 degrees, termed the reverse...
125
Circuit Breaker and Fuse Selection01:23

Circuit Breaker and Fuse Selection

A circuit breaker is a device engineered to interrupt fault currents and sometimes reclose automatically. When a fault current is detected, the breaker separates the electrical contacts, which generates an arc. This arc is extinguished by methods such as elongation, cooling, or splitting, depending on the breaker's design. Breakers are categorized based on the voltage they operate at and the medium used for arc extinction, such as air, oil, SF6 gas, or vacuum.
In high-voltage systems,...
110