Residual LSTM-based short duration forecasting of polarization current for effective assessment of transformers
Aniket Vatsa1, Ananda Shankar Hati1, Prashant Kumar2
1Department of Electrical Engineering, Indian Institute of Technology (Indian School of Mines), Dhanbad, 826004, India.
Abstract:
The empirical application of polarization and depolarization current (PDC) measurement of transformers facilitates the extraction of critical insulation-sensitive parameters. This technique, rooted in time-domain dielectric response analysis, forms the bedrock for parameterization and insulation modeling. However, the inherently time-consuming nature of polarization current measurements renders them susceptible to data corruption. This article explores deep-learning-based short-duration techniques for forecasting polarization current to address this limitation. By incorporating spatial shortcuts, the residual long short-term memory (LSTM) network facilitates the seamless propagation of spatial and temporal gradients. Furthermore, the relative forecasting assessment of the proposed residual LSTM model's performance is made against traditional LSTM, attention LSTM, gated recurrent units (GRU), and convolutional neural network (CNN) models. Thus, optimal model selection strategies are evaluated based on their capability to capture extended dependencies and short-term information present in the data. In addition, the Monte Carlo dropout prediction is employed to estimate uncertainty in polarization current forecasts. The findings demonstrate that the proposed residual LSTM network model for polarization current forecasting yields the lowest error metrics and maintains prediction consistency over the testing duration. Thus, the proposed approach significantly reduces PDC measurement time, providing an effective means to develop proactive maintenance strategies for evaluating the insulation condition of transformers.
Related Concept Videos
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Insulation Coordination
Power System Three-Phase Short Circuits
Transformers
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...