Transformer hot spot temperature estimation through adaptive neuro fuzzy inference system approach

Edwell T Mharakurwa1, Dorothy W Gicheru1

  • 1Department of Electrical & Electronic Engineering Dedan Kimathi University of Technology (DeKUT), Private Bag, 10 143, Nyeri, Kenya.

Heliyon
|February 23, 2024
PubMed
Summary

This study introduces an adaptive neuro-fuzzy inference system (ANFIS) to accurately estimate power transformer winding hot spot temperatures (HST). The ANFIS model enhances transformer reliability and asset management by improving thermal analysis accuracy.

Related Concept Videos

Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
152
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
873
Transformers01:26

Transformers

A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
1.1K
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
85
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
102
Thermosensation01:43

Thermosensation

Peripheral thermosensation is the perception of external temperature. A change in temperature (on the surface of the skin and other tissues) is detected by a family of temperature-sensitive ion channels called Transient Receptor Potential, or TRP, receptors. These receptors are located on free nerve endings. Those detecting cold temperatures are closer to the surface of the skin than the nerve endings detecting warmth. These thermoTRP channels, while temperature selective, have relatively...
30.4K