Hybrid Multi-Infeed Receiver Line Longitudinal Protection Scheme Based on Voltage Waveform Comprehensive Distance
Shuping Gao1,2, Xiaofang Li1,2, Guobing Song3
1Department of Electrical and Control Engineering, Xi'an University of Science and Technology, Xi'an 710054, China.
Abstract:
The coupling of AC and DC power will impact the protective actions on the AC side and pose a threat to the stable operation of the interconnection system. Therefore, a new longitudinal protection method is proposed based on the comprehensive distance similarity of voltage waveforms. Initially, the measured voltage and current data are extracted to calculate the reference voltage, and the voltage waveform fitting is optimized. Subsequently, the Euclidean dynamic time warp (DTW) distance and entropy weight method are utilized to process the voltage waveform, enabling the calculation of its comprehensive distance similarity. This similarity is adopted to determine fault location. A hybrid DC multi-feed AC/DC interconnection system, incorporating a line commutated converter-voltage source converter (LCC-VSC) and a line commutated converter-modular multilevel converter (LCC-MMC), was established in PSCAD, and fault data were simulated and output. The effectiveness of the protection scheme was validated using MATLAB. Simulation results demonstrate that the proposed method can accurately distinguish between faults inside and outside a region. When compared to existing protection methods, it demonstrates superior performance in resisting transition resistance and noise interference, while also mitigating the impact of data asynchronicity. The speed and reliability of the method are further enhanced.
More Related Videos
07:43A Simple Approach to Perform TEER Measurements Using a Self-Made Volt-Amperemeter with Programmable Output Frequency
Published on: October 5, 2019
07:14Tracking Infiltration Front Depth Using Time-lapse Multi-offset Gathers Collected with Array Antenna Ground Penetrating Radar
Published on: May 1, 2018
Related Concept Videos
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Differential Relays
Radial System Protection
In a radial system with a fault downstream of the third breaker, ideally, only the third breaker will open, isolating the fault and interrupting the load connected beyond it. The second breaker has a longer delay setting,...
Boundary Conditions: Lossless Lines
At the receiving end, the boundary condition states that the voltage equals the product of the receiving-end impedance and current. This relationship is expressed as a function of the incident and...
Power System Three-Phase Short Circuits
Zones of Protection
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...