Research on transformer fault diagnosis method based on ACGAN and CGWO-LSSVM
Shan Guan1, Tong-Yu Wu2, Hai-Qi Yang1
1School of Mechanic Engineering, Northeast Electric Power University, Jilin, 132012, China.
Abstract:
This paper proposes a transformer fault diagnosis method based on ACGAN and CGWO-LSSVM to address the problem of misjudgment and low diagnostic accuracy caused by the small number and uneven distribution of some fault samples in transformer fault diagnosis. Firstly, generate adversarial networks through auxiliary classification conditions, The ACGAN method expands a small and imbalanced number of samples to obtain balanced and expanded data; Secondly, the non coding ratio method is used to construct the characteristics of dissolved gases in oil, and kernel principal component analysis is used, KPCA method for feature fusion; Finally, using the improved cubic gray wolf optimization algorithm, CGWO for least square support vector machines, optimize the parameters of the LSSVM model and construct a transformer fault diagnosis model. The results show that the proposed method has a low false alarm rate and a diagnostic accuracy of 97.66%, compared to IGOA-LSSVM the IChOA-LSSVM and PSO-LSSVM methods improved accuracy by 0.12, 1.76, and 2.58%, respectively. This method has been proven to solve the problems of misjudgment and low diagnostic accuracy caused by small sample sizes and uneven distribution. It is suitable for multi classification fault diagnosis of transformer imbalanced datasets and is superior to other methods.
Related Concept Videos
Power System Three-Phase Short Circuits
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Fault Types
For line-to-line faults occurring between phases B and C, the...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Transformers with Off-Nominal Turns Ratios