Fault diagnosis method for oil-immersed transformers integrated digital twin model

Haiyan Yao1, Xin Zhang2, Qiang Guo1

  • 1Hangzhou Electric Power Equipment Manufacturing Co. Ltd Yuhang Qunli Complete Sets Electricity Manufacturing Branch Electric, Hangzhou, 311000, China.

Scientific Reports
|September 2, 2024
PubMed
Summary

This study introduces a novel digital twin-integrated fault diagnosis method for oil-immersed transformers, achieving 98.1013% accuracy. The approach enhances transformer maintenance through improved state perception and real-time collaboration.

Related Concept Videos

Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
142
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
78
Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
216
Instrument Transformers01:23

Instrument Transformers

Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
76
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
99
Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
401