Application of a Coupling Agent to Improve the Dielectric Properties of Polymer-Based Nanocomposites
Published on: September 19, 2020
Improving the distribution system capability by incorporating ZnO nanoparticles into high-density polyethylene cable
Mahmoud A Elsadd1, Ragab A Elsad2, Maryam Al Huwayz3
1Electrical Engineering Department, Faculty of Engineering, Damanhour University, Damanhour, Egypt.
Abstract:
This paper introduces a novel insulated cable designed to enhance the distribution system's capabilities. Accordingly, high-density polyethylene loaded with varying concentrations of zinc oxide (ZnO) nanoparticles (NPs) ranging from 0.0 to 5 wt% was prepared using the melt-blending technique. Zinc oxide (NPs) is synthesized by using sol-gel technique and their microstructure was examined by X-ray diffraction. The new insulated cable, HDPE nanocomposite loaded with 1 wt% of ZnO, demonstrates a 43% reduction in the relative dielectric constant and a 16.5% improvement in breakdown strength compared to pure HDPE. The observed changes in both the dielectric constant and breakdown strength offer several advantages in electrical applications. These benefits include a decrease in feeder current at the same loading level, mitigation of inrush transients during load switching, and a reduction in earth fault current values, particularly in unearthed distribution networks with ungrounded cables. A comparative study is conducted between the conventional insulating cable based on the original material (HDPE) and the new insulated cable incorporating ZnO nanomaterial at a ratio of 1.0 wt% of the total cable mass per unit length. This comparison utilizes data from two actual medium-voltage distribution feeders. Both actual feeders are simulated using the EMTP/ATP package. The obtained results prove the efficacy of the developed material cable (polymer doped with ZnO NPs) compared to the base material. The peak and duration of inrush current can be cut to 77.3% and 67% of their original values, respectively. The earth fault current can be reduced to 56.5% in ungrounded networks, while substation current under the normal operation can be cut to 84.3% with the same load currents.
More Related Videos
07:28Ethylene Polymerizations Using Parallel Pressure Reactors and a Kinetic Analysis of Chain Transfer Polymerization
Published on: November 27, 2015
08:33Functionalization and Dispersion of Carbon Nanomaterials Using an Environmentally Friendly Ultrasonicated Ozonolysis Process
Published on: May 30, 2017