Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers
Yukun Ma1, Xiu Zhou1, Xiaokang Wang2
1Electric Power Research Institute, State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750011, China.
Abstract:
The short-circuit withstanding capability of a transformer is a critical indicator for evaluating its operational reliability. This study investigates the influence of the low-voltage winding height, a key structural parameter, on the electromagnetic forces induced by short-circuit currents and the resultant short-circuit withstand capability. First, theoretical calculation formulas for the transformer leakage magnetic field and winding electromagnetic forces were derived, establishing a foundation for subsequent analysis. Subsequently, two 110 kV transformers, identical in all structural parameters except for their low-voltage winding heights, were selected as case studies. Three-dimensional finite element models were constructed to perform detailed simulations and a comparative analysis of the leakage magnetic field distribution and electromagnetic forces under short-circuit conditions. Finally, practical short-circuit tests were conducted on both transformers for experimental validation, monitoring and comparison of their short-circuit reactance variation curves. Furthermore, a CNN-LSTM model, utilizing the winding axial height of a 110 kV three-phase three-limb transformer as the characteristic parameter, is developed to detect short-circuit fault damage in such transformers with varying winding heights. Through a combined approach of theoretical analysis, simulation, and experimental verification, this study confirms that the low-voltage winding height was a crucial factor affecting the transformer's short-circuit withstand capability of the transformer. Studies have shown that with the increase in the height of low-voltage windings, the leakage magnetic flux of the low-voltage windings increases by 36%, the radial electromagnetic force increases by 37.5%, and the axial electromagnetic force increases by 8.5%. Excessively tall windings amplify radial electromagnetic forces, compromising mechanical stability and consequently increasing the risk of damage during short-circuit faults.
Related Concept Videos
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
Power System Three-Phase Short Circuits
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Insulation Coordination
Transformers in Distribution System
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...