A High-Impedance Grounding Fault Identification Method for Mining Cables in Non-Effectively Grounded Systems of Coal
Chen Feng1, Long Ni1, Yunfeng Lan1
1The College of Electrical Engineering and Automation, Shandong University of Science and Technology, Qingdao 266590, China.
Abstract:
In coal mine non-solidly grounded systems, high-impedance faults generate minimal zero-sequence currents with obscured characteristics and strong interference, complicating faulted line identification. Existing methods rarely address three-phase imbalance and variable cable parameters, causing selection errors. To this end, a method for identifying the non-effective ground fault routing of mining cables based on Steady-State Impedance Analysis (SSIA) and Holmes-Duffing oscillator small-signal detection is proposed. Firstly, based on SSIA, the mapping relationship that the phase of the zero-sequence current variation in the faulted line is the same as the phase of its voltage relative to the faulted ground is derived before and after the occurrence of the fault. Meanwhile, identifiable differences exist in both phase and amplitude of the zero-sequence current change in faulty lines compared to non-faulty lines before and after fault occurrence. This is used as the criterion for high-impedance ground fault line selection. In the mining environment, zero-sequence current variations are characterized as weak signals, which poses significant challenges for detection. Thus, a Holmes-Duffing oscillator weak signal detection method is proposed. Based on chaotic principles, accurate line selection is achieved by diagnosing chaotic states in oscillator-generated phase trajectories. A specific mine grid simulation via MATLAB/Simulink 2023b validates the method's efficacy and applicability.
Related Concept Videos
Series Impedances: Three-Phase Line
Using Kirchhoff's laws, an integro-differential equation for the network is derived. This equation accounts for unbalanced phase currents, which may induce return currents through neutral wires and the earth, seeking the least impedance path. Earth return conductors can replace the...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Power System Three-Phase Short Circuits
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Fault Types
For line-to-line faults occurring between phases B and C, the...
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...