Unintended tripping of healthy parallel lines during single-line-to-ground faults: field evidence and mitigation
Farhad Aghajanian Sabagh1, Farzad Hajimohammadi1,2, Bahador Fani3
1Akhtar Bargh Isfahan Company, Isfahan, Iran.
Abstract:
Distance relays may maloperate under various conditions such as improper settings, measurement distortion, or abnormal network operating states. This article investigates an overlooked mechanism leading to distance relay maloperation in parallel sub-transmission circuits containing underground cable sections. During a single-phase-to-ground fault on one circuit, a portion of the fault current may return through the neutrals of receiving-end transformers and flow back toward the source through the parallel healthy circuit. This reverse fault current component can become aligned with the load current of a healthy phase, resulting in a significant reduction of the apparent impedance measured by the distance relay. Consequently, the impedance trajectory may enter the relay operating characteristic from the load region, causing undesired zone operation and tripping of the healthy line. Such a misoperation may lead to simultaneous disconnection of both parallel circuits and severe downstream outages, despite the fault being confined to only one line. The mechanism is analytically explained and validated using disturbance records from a real 63 kV network. In addition, DIgSILENT PowerFactory simulations are conducted to reproduce the observed behavior and confirm the current amplification. Key factors influencing the severity of the phenomenon, including cable shield grounding conditions and fault proximity to the receiving-end substation, are also discussed. Finally, practical countermeasures are proposed to improve protection security and prevent unnecessary tripping.
Related Concept Videos
Fault Types
For line-to-line faults occurring between phases B and C, the...
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Power System Three-Phase Short Circuits
Directional Relays
Lossy Lines and Overvoltages
Attenuation
When constant series resistance and shunt conductance are present, voltage and current equations are modified. The propagation constant indicates that voltage and current waves consist of both forward and backward traveling components. These waves attenuate as they propagate, with the attenuation factor related to the resistance and conductance. In a...