Design optimization and electromagnetic performance investigation of a magnetically integrated transformer-type

Xi Wang1, Mowei Shen1, Pengyu Fu2

  • 1Inner Mongolia University of Technology, Hohhot City, 010080, Inner Mongolia Autonomous Region, China.

Scientific Reports
|July 13, 2026
PubMed
Abstract

Related Concept Videos

Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The winding...
Control of Power Flow01:30

Control of Power Flow

There are several methods to control power flow in power systems:
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the copper windings...
Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
The Ideal Transformer01:26

The Ideal Transformer

In single-phase two-winding transformers, two windings are coiled around a magnetic core characterized by cross-sectional area A and magnetic permeability μ. A phasor current i1 enters the left winding while i2 exits the right winding, establishing the fundamental working of the transformer through electromagnetic principles.
Ampere's Law forms the basis of understanding the magnetic field within the transformer. It states that the integral of the magnetic field intensity's tangential component...
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the rated...