[Air microbiology monitoring in plenum-ventilated operating rooms. Proposed standards]

C Gaspar1, M J Calvente, C Fernández

  • 1Servicio de Medicina Preventiva, Hospital Universitarío San Carlos, Madrid.

Abstract

Insights

Microbiological air contamination in operating theatres decreased significantly over five years. This study established new microbiological standards for plenum-ventilated operating theatres, improving hygiene.

Area of Science:

  • Environmental Microbiology
  • Hospital Infection Control
  • Healthcare Engineering

Background:

  • Microbiological air standards for plenum-ventilated operating theatres are undefined.
  • Analysis of air contamination in HUSC theatres was conducted to establish reference standards.

Purpose of the Study:

  • To analyze microbiological air contamination in HUSC operating theatres.
  • To establish microbiological reference standards for plenum-ventilated theatres.

Main Methods:

  • 408 air samples collected from air intake and theatre centers (1991-1995).
  • RCS air sampler used; microbiological counts compared using ANOVA and Kruskal-Wallis tests.
  • Standards based on upper confidence limits of counts from consecutive years with similar contamination levels.

Main Results:

  • Observed a statistically significant falling trend in microbiological counts (1992 vs. 1994-1995).
  • Significant difference in contamination between air intake and theatre centers (p < 0.01).
  • Significant decrease in fungal presence observed (p = 0.001).

Conclusions:

  • The control program evaluated and improved operating theatre hygiene.
  • Established microbiological reference standards for plenum-ventilated operating theatres.
  • Demonstrated the effectiveness of monitoring in enhancing air quality.