研究风力发电透极限,考虑到电压稳定性的研究.
Xiaofei Liu1, Yihan Zhang2, Huixuan Li2
1State Grid Henan Economic Research Institute, Zhengzhou, 450000, China. heytea0108@163.com.
Scientific reports
|January 7, 2026
概括
本研究引入了一种新方法,通过分析电压稳定性来确定电网可处理的最大风力发电容量. 该方法准确地估计了风力发电透极限 (WPPL),这对于电网规划至关重要.
科学领域:
- 电气工程 电气工程
- 电力系统分析 分析 分析
背景情况:
- 越来越多的风力发电集成挑战了电网稳定性.
- 电网电压稳定性是限制风电容量的关键因素.
研究的目的:
- 开发一种新的方法来评估风力发电透极限 (WPPL),考虑到电压稳定性.
- 为电网规划提供快速有效的WPPL估计.
主要方法:
- 使用减少序的雅可比矩阵来分析风力发电影响的模态固有值.
- 提出基于电压稳定性约束的WPPL分析计算方法.
主要成果:
- 拟议的方法准确地估计了模拟和现实世界电力系统中的WPPL.
- 案例研究证实了与现有方法相比,该方法的有效性.
结论:
- 开发的方法提供了一种可靠的方法来评估WPPL,考虑到电压稳定性.
- 分析确定了影响WPPL的关键因素,并提出了改进的工程措施.
相关概念视频
Maximum Power Flow and Line Loadability
582
The maximum power flow for lossy transmission lines is derived using ABCD parameters in phasor form. These parameters create a matrix relationship between the sending-end and receiving-end voltages and currents, allowing the determination of the receiving-end current. This relationship facilitates calculating the complex power delivered to the receiving end, from which real and reactive power components are derived.
582
Generator Voltage Control
617
Generator voltage control is crucial for maintaining the stable operation of synchronous generators and wind turbines. In older models, a DC generator driven by the rotor delivers DC power to the rotor's field winding, and the power is transferred through slip rings and brushes. In the latest models, static or brushless exciters are used. Static exciters rectify AC power from the generator terminals and then transfer the DC power directly to the rotor. Brushless exciters, on the other hand, use...
617
Turbine-Governor Control
921
Turbine-governor control is crucial for maintaining power system stability by balancing turbine mechanical power output with electrical load demand. This mechanism ensures that generator frequency and rotor speed are within acceptable limits during load variations. Turbine-generator units store kinetic energy due to their rotating masses; this energy is released to meet the load requirement when the load increases. The electrical torque of turbines rises to meet the demand, whereas the...
921
Wind Turbine Machine Models
557
In the growing field of wind energy, incorporating wind turbine models into transient stability analysis is essential. Induction and synchronous machines are the primary models used, with induction machines being prevalent due to their simplicity and reliability.
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
557
Generation of Three-Phase Voltage
744
A three-phase AC generator has a rotor with a rotating magnet placed within the stator mounted with the stationary three-phase winding to generate three-phase voltages via mutual induction. These windings are evenly distributed around the inner circumference of the stator and are arranged 120 electrical degrees apart. Three-phase stator windings consist of three separate coils or groups of coils, known as phases, each connected in Y (star) configuration or Delta configuration.
As the rotor...
As the rotor...
744
Multimachine Stability
539
Multimachine stability analysis is crucial for understanding the dynamics and stability of power systems with multiple synchronous machines. The objective is to solve the swing equations for a network of M machines connected to an N-bus power system.
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
539