Related Experiment Video
Updated: Jun 23, 2026

04:35
Comparative Study of Simulation of Temperature Rise in Ring Main Unit
Published on: July 5, 2024
Leakage reduction for the Siemens Moduleaf.
1Department of Radiation Oncology, University of Iowa Hospitals and Clinics, Iowa City, Iowa, U.S.A.
Journal of Applied Clinical Medical Physics
|May 22, 2009
Summary
Modifications to the Moduleaf add-on miniature multileaf collimator (MMLC) improved leakage dose accuracy. Filling frame gaps and adjusting Siemens MLC operation reduced discrepancies in leakage patterns and improved treatment planning system modeling.
Area of Science:
- Medical Physics
- Radiation Oncology
Background:
- The Moduleaf add-on miniature multileaf collimator (MMLC) for Siemens Oncor linear accelerators offers high-resolution field shaping.
- Anisotropy in leakage and scatter dose distributions along the x and y axes, and significant inter-leaf leakage, present challenges for accurate modeling in treatment planning systems.
Purpose of the Study:
- To address discrepancies in leakage and scatter dose distributions observed with the Moduleaf MMLC.
- To improve the accuracy of dose modeling for the Moduleaf MMLC within the Pinnacle treatment planning system.
Main Methods:
- Gaps in the Moduleaf frame were filled with lead sheets.
- The Siemens MLC was operated in MLC mode, with leaves closed behind the Y jaws, to create a defined rectangular field.
- Leakage and scatter dose distributions were measured and compared to Pinnacle treatment planning system profiles.
Main Results:
- The modifications significantly reduced the difference between x-axis and y-axis leakage patterns.
- Maximum leakage doses outside the treatment region were reduced to 0.43%.
- The mean square error between calculated and measured dose profiles in the tail region was reduced.
Conclusions:
- Modifications to the Moduleaf MMLC effectively resolved issues with anisotropic leakage and scatter dose distributions.
- The implemented changes enhance the accuracy of dose calculations for radiation therapy planning involving the Moduleaf MMLC.
Related Concept Videos
Reducing Line Loss
In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
Energy Losses in Transformers
In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality, the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the copper windings...
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the copper windings...
Block Diagram Reduction
The process of deriving the transfer function of a control system often involves reducing its block diagram to a single block. This simplification can be achieved through a series of strategic operations, including relocating branch points and comparators. These operations preserve the overall function of the system while allowing for easier manipulation and combination of blocks.
The first step in this process is the identification and relocation of a branch point. A branch point, where a...
The first step in this process is the identification and relocation of a branch point. A branch point, where a...
Line Loss
The different configurations of source-load connections include wye (star) and delta connections. The relationship between line and phase voltages and currents varies depending on the configuration. When the source is supplying power, it is transmitted through the wires to the load, and during this transmission, some power is absorbed by the wires, leading to line loss.
Line loss impacts power delivery efficiency in a balanced three-phase circuit. The symmetry in such a circuit simplifies the...
Line loss impacts power delivery efficiency in a balanced three-phase circuit. The symmetry in such a circuit simplifies the...
Power System Three-Phase Short Circuits
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
Line Protection with Impedance Relays
Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
Under normal conditions, low load currents keep the measured...

