Leakage reduction for the Siemens Moduleaf.

R Alfredo Siochi1

  • 1Department of Radiation Oncology, University of Iowa Hospitals and Clinics, Iowa City, Iowa, U.S.A.

Summary

Modifications to the Moduleaf add-on miniature multileaf collimator (MMLC) improved leakage dose accuracy. Filling frame gaps and adjusting Siemens MLC operation reduced discrepancies in leakage patterns and improved treatment planning system modeling.

Related Concept Videos

Reducing Line Loss01:18

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the copper windings...
Block Diagram Reduction01:22

Block Diagram Reduction

The process of deriving the transfer function of a control system often involves reducing its block diagram to a single block. This simplification can be achieved through a series of strategic operations, including relocating branch points and comparators. These operations preserve the overall function of the system while allowing for easier manipulation and combination of blocks.
The first step in this process is the identification and relocation of a branch point. A branch point, where a...
Line Loss01:10

Line Loss

The different configurations of source-load connections include wye (star) and delta connections. The relationship between line and phase voltages and currents varies depending on the configuration. When the source is supplying power, it is transmitted through the wires to the load, and during this transmission, some power is absorbed by the wires, leading to line loss.
Line loss impacts power delivery efficiency in a balanced three-phase circuit. The symmetry in such a circuit simplifies the...
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
Line Protection with Impedance Relays01:27

Line Protection with Impedance Relays

Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...