Related Experiment Video
Updated: May 13, 2026

Comparative Study of Simulation of Temperature Rise in Ring Main Unit
Published on: July 5, 2024
Comparison of model-based and conventional controllers on a pilot-scale heat exchanger
Pramod R Raul1, Haritha Srinivasan, Sanket Kulkarni
1School of Mechanical & Aerospace Engineering, Oklahoma State University, OSU, Stillwater, OK 74078-5021, USA.
Abstract:
This pilot-scale heat exchanger demonstration compares two relatively simple nonlinear model-based control strategies to conventional proportional-integral (PI) control. The two nonlinear controllers, generic model control (GMC) and process-model based control (PMBC), use a first-principles model thereby providing characterization of the nonlinear process throughout the operating range. There are two approaches to GMC, one uses a dynamic model, the other a steady-state model. This work uses the steady-state model; accordingly, will use the term GMC-SS, which can be classified as output characterization for a PI controller, making it relatively simple to implement. PMBC uses a dynamic model and adapts to represent the process. These two nonlinear controllers were selected for this application evaluation because of their simplicity (they can be implemented in-house within many commercial control systems), diversity (steady-state and dynamic models), and demonstrated utility for control of nonlinear single-input-single-output processes. The application and results are presented and discussed. Summarizing the results: Within a small temperature operating range PI provides good control, but over the full operating range, the nonlinear and variable delay of the process lead to poor control with PI. GMC can handle the nonlinear issues, but using the convenient steady-state model; it also, provides poor control because of the variable delay associated with flow rate. PMBC was able to provide good control throughout the entire operating range. PMBC has a further advantage of only having one tuning coefficient, while PI and GMC-SS have two.
Related Concept Videos
PID Controller
Controller Configurations
Control-system compensation involves various configurations, most commonly series or cascade compensation, in which the controller aligns...
Open and closed-loop control systems
An open-loop control system operates without feedback from the output. It consists of two primary elements: the controller and the controlled process. The controller receives an input signal and...
Mechanisms of Heat Transfer II
Mechanisms of Heat Transfer I
Typical Model Studies