Modelling and Optimization of Four-Segment Shielding Coils of Current Transformers

Yucheng Gao1, Wei Zhao2, Qing Wang3

  • 1Department of Electrical Engineering, Tsinghua University, Beijing 100084, China. yuchengg@gmail.com.

Summary

Shielding coils effectively protect generator current transformers (CTs) from magnetic interference. This study presents an analytical model for optimizing shielding coil design, validated by experiments.

Related Concept Videos

Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
1.5K
Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
834
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
615
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
1.4K
Reducing Line Loss01:18

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
406
Calculation of Self-inductance01:29

Calculation of Self-inductance

The self-inductance of a circuit, often simply called the inductance, is a purely geometric factor that depends only on the circuit component's structure. More specifically, it depends on the shape and size of the component that lets the flux pass through it, thus inducing an electric field that opposes any current passing through it.
Since the effect of the induced electric field and the back EMF generated depends on the rate of change of current and the self-inductance, the inductance...
919