Comparison of operating room air distribution systems using the environmental quality indicator method of dynamic
Jennifer A Wagner1, Damon G Greeley1, Thomas C Gormley2
1OnSite-LLC, Indianapolis, IN.
Background:
Ensuring aseptic airborne environments for sterile fields and back instrument tables in operating rooms (ORs) is crucial to reducing microbial and particle contamination during surgery. Configurations of in-ceiling air delivery mechanisms impact the effectiveness of the system at eliminating contamination in critical zones.
Methods:
The environmental quality indicator method was used to assess airborne environments in ORs equipped with a single large diffuser (SLD), a multidiffuser array (MDA), or a 4-way throw diffuser during dynamic, simulated surgical procedures. Environmental quality indicators measured included particles, microbes, carbon dioxide, velocity, humidity, and temperature at 26 air changes per hour.
Results:
SLD ORs performed better than MDA ORs and 4-way throw diffuser ORs at removing microbes and carbon dioxide from the sterile field (P < .05). SLD ORs had higher velocity and lower temperature over the sterile field than the other 2 ORs (P < .05). MDA ORs had lower total particle counts than the other ORs (P < .05). The sterile fields in all ORs were cleaner than the respective back instrument tables (P < .05).
Conclusions:
Air delivery systems that eliminate blockages to uniform airflow directly over sterile zones, such as boom mounts and access panels, and deliver unidirectional, downward flow of clean filtered air provided a cleaner airborne environment within the sterile field. Expansion of air delivery systems to include areas outside the sterile field, where other surgical aides reside, may further reduce contamination within critical zones.
More Related Videos
05:47Simulation of a Scaled Assembly Process with Collaboration of a Robotic Arm and Monitoring through a Vision System for Quality Control
Published on: August 29, 2025
05:45Composition and Distribution Analysis of Bioaerosols Under Different Environmental Conditions
Published on: January 7, 2019
Related Concept Videos
Indicators
Kidney Transplant II: Surgical Procedure
Renal Drug Clearance: Comparison Between Renal Excretion Methods
Renal clearance is often associated with the renal glomerular filtration rate (GFR), which represents the rate at which plasma is filtered through the glomeruli in the kidney. When drug reabsorption is minimal and there is no active secretion, renal clearance is closely related to the...
The Sense of Self: Reflected Self-Appraisal and Social Comparison
Quality Control
Quality control helps track data, visualize trends, and identify variations, making it easier to detect deviations that may affect the accuracy of an analysis. One way to do this is by generating a quality control chart, which...
Quality Assurance