Calibration Procedure to Test the Effects of Multiple Influence Quantities on Low-Power Voltage Transformers
Alessandro Mingotti1, Lorenzo Peretto1, Roberto Tinarelli1
1Department of Electrical, Electronic and Information Engineering-Guglielmo Marconi, Alma Mater Studiorum-University of Bologna, Viale del Risorgimento, 240136 Bologna, Italy.
Abstract:
The article presents a study on low-power voltage transformers (LPVTs). Considering their increasing spread among Smart Grids, it is fundamental to assess their accuracy behavior in as realistic conditions as possible. Therefore, this article presents a detailed calibration procedure to test LPVTs' accuracy when various external influence quantities are simultaneously acting on them. In the calibration procedure, the considered quantities are frequency, air temperature, and external electric field. Afterwards, the designed procedure is applied on three different off-the-shelf LPVTs using a measurement setup developed in a laboratory environment. The presented results (i) confirm the easy applicability of the designed calibration procedure; (ii) highlight the various effects of the influence quantities on the accuracy of different types of LPVTs; (iii) confirm the need to include more realistic tests, like the type-tests presented, into the standards to appreciate a wider set of possible in-field behaviors.
Related Concept Videos
Transformers
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
Types Of Transformers
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
Reducing Line Loss
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
Transformers with Off-Nominal Turns Ratios
Instrument Transformers