Quantifying the Relative Thickness of Conductive Ferromagnetic Materials Using Detector Coil-Based Pulsed Eddy Current Sensors
Published on: January 16, 2020
Non-Contact Current Measurement for Three-Phase Rectangular Busbars Using TMR Sensors
Huafeng Su1, Haojun Li1, Weihao Liang1
1Dongguan Power Supply Bureau of Guangdong Power Grid Co., Ltd., Dongguan 523120, China.
This study introduces a non-contact current measurement method using tunneling magneto-resistance (TMR) sensors for three-phase busbars. The system achieves high accuracy with less than 2.5% RMS error and 1° phase error, enabling reliable power monitoring.
Area of Science:
- Electrical Engineering
- Sensor Technology
- Power Systems
Background:
- Accurate current measurement is crucial for power system monitoring and control.
- Existing non-contact methods often face limitations in dynamic range, bandwidth, or installation complexity.
- Three-phase rectangular busbars require specialized non-contact sensing solutions.
Purpose of the Study:
- To develop and validate a novel non-contact current measurement method for three-phase rectangular busbars.
- To utilize the advantages of tunneling magneto-resistance (TMR) sensors for enhanced measurement performance.
- To achieve accurate and reliable online calibration of the current sensor system.
Main Methods:
- A non-contact current sensor array using three TMR sensors was designed and positioned near busbars.
- A thyristor-controlled resistive load was employed for generating identifiable calibration currents.
- A robust method was developed to extract voltage components from TMR sensor signals for calibration.
- A complete measurement system integrating the TMR sensor, calibrator, and data acquisition was implemented.
Main Results:
- The developed system demonstrated a relative RMS error of less than 2.5% and a phase error of less than 1° compared to a commercial probe.
- Nonlinearity error of the TMR-based current sensor was found to be better than 0.8%.
- The proposed online calibration method proved effective in establishing accurate current-to-magnetic field relationships.
Conclusions:
- The proposed non-contact current measurement method using TMR sensors is accurate and reliable for three-phase rectangular busbars.
- The system's performance, including low error margins and effective online calibration, makes it suitable for practical power distribution applications.
- TMR sensors offer a viable solution for non-contact current sensing due to their favorable characteristics.
More Related Videos
Related Concept Videos
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Power System Three-Phase Short Circuits
Three-Phase Circuits
Magnetic Force On Current-Carrying Wires: Example
Three-Phase Voltages