Research on transformer fault diagnosis models with feature extraction

Yongcan Zhu1, Zhenyan Guo1, Xiaoxuan Zhan2

  • 1College of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.

PubMed
Summary

This study introduces an Artificial Hummingbird Algorithm (AHA)-optimized Kernel Principal Component Analysis (KPCA) and Extreme Learning Machine (ELM) for transformer fault diagnosis. The novel AHA-KPCA-ELM method significantly improves diagnostic accuracy, achieving 95.73%.

Related Concept Videos

Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
77
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
139
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
831
Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
199
Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
396
Fault Types01:18

Fault Types

When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.
For line-to-line faults occurring between phases B and C, the...
75