Related Experiment Video
Updated: Jun 6, 2025

Author Spotlight: Simulation and Analysis of the Temperature Rise of Ring Main Unit Equipment
Published on: July 5, 2024
Radiated and conducted research on damage characteristics of digital protective relays in substations under
Fangzheng Wu1, Junna Li1, Qixiang Huang1
1State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University, Xi'an 710024, People's Republic of China.
Abstract:
This paper presents the damage characteristics of digital protective relays (DPR) in substations under high-altitude electromagnetic pulse (HEMP) environments through radiated and conducted tests. Three representative substation circuits of DPR are selected, and the radiated and conducted experiments are performed. Through a comprehensive analysis of the radiated and conducted test results, the damage characteristics of DPRs under the HEMP environment are determined, including port coupling characteristics and vulnerability, respectively. The results can be summarized as follows: the current acquisition port and the power supply port demonstrate excellent surge protection capabilities, effectively suppressing both the peak and width of the surge voltage, which endure the maximum radiated field intensity level and injection voltage level without suffering damage. In contrast, the gas protection port of the gas protection circuit lacks the capability to suppress surge voltage peaks, resulting in a higher probability of port damage and experiencing unrecoverable damage at a radiated field intensity level of 50 kV/m and injection voltage levels of 20 and 30 kV. Overall, the results of radiated and conducted experiments provide references for DPR equipment protection and comprehensive substation protection.
Related Concept Videos
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Overcurrent Relays
Instantaneous overcurrent relays activate immediately when the input current exceeds a predetermined value, known as the pickup current, instantly energizing the circuit breaker trip coil. This rapid response is vital for addressing severe faults quickly.
Time-delay overcurrent relays, on the other...
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Differential Relays
Radial System Protection
In a radial system with a fault downstream of the third breaker, ideally, only the third breaker will open, isolating the fault and interrupting the load connected beyond it. The second breaker has a longer delay setting,...
Pilot and Numeric Relaying