Simplified and Low-Cost Characterization of Medium-Voltage Low-Power Voltage Transformers in the Power Quality
Alessandro Mingotti1, Christian Betti1, Lorenzo Peretto1
1Department of Electrical, Electronic and Information Engineering, Guglielmo Marconi Alma Mater Studiorum, University of Bologna, Viale del Risorgimento 2, 40136 Bologna, Italy.
Abstract:
The distribution network is experiencing a massive deployment of intelligent electronic devices (IEDs) such as energy meters, protective devices, and phasor measurement units (PMUs). This phenomenon resulted, on the one hand, in (i) the availability of distributed measurement systems capable of monitoring and collecting measurements from the distribution network, and (ii) increasing awareness of the system operator about the status of the network. On the other hand, such a significant number of devices require to be characterized, over the years, and assessed in both sinusoidal and distorted conditions. However, the characterization process may require a huge investment of money and time considering the low availability of reference instruments and accredited laboratories. To this purpose, this paper presents a simple and fast test procedure, performed with cheap and low-voltage instrumentation, to characterize two off-the-shelf low-power medium-voltage sensors in the power quality frequency range. In detail, the paper describes the measurement setup developed for the characterization and the performed tests. In addition, the method was also reproduced with reference equipment for validation purposes. Lastly, for both tests, an uncertainty evaluation was performed to quantify the goodness of the proposed method. From the results, it is possible to appreciate that the designed cheap and simple test can achieve as accurate results as those of a sophisticated and expensive equipment.
Related Concept Videos
Instrument Transformers
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Transformers with Off-Nominal Turns Ratios
Transformers in Distribution System
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...